CWSS to Gingee - Ananthapuram Rtp and 11 Other Habitations In Mugaiyur and Kanai Unions in Villupuram District.

Section: Combined Water Supply Schemes acivements pages are not under access control

Salient Details

Name of Scheme : CWSS to Gingee - Ananthapuram Rtp and 11 Other Habitations In Mugaiyur and Kanai Unions in Villupuram District
Project Cost : Rs. 638 Lakhs.
Beneficiaries :
  • Gingee and Ananthapuram TP
  • Habitations : 11 Nos
Population : 79000
Total Daily Requirement : 3.72 mld
Hours of Pumping : 16 Hours
Source : River Thenpennaiyar near Nerkunam Village

Head Works

Infiltration Well Yield : 4 Nos. of 4.5 m dia 1000 lpm in each
Collection Well : 11,30,000 Lit. Capacity
Pumpset : 5 Nos.of 3 HP Submersible Pumpset(1 as stand bye) Duty : 5578 lpm x 23m Head.
Connecting Main
From well No.1
From well No.2
From well No.3 From well No.4
: 150mm dia CI pipes
195 m
132 m
245 m
620 m

Pumping Main: : Reach-I

350mm.AC Cl.10 pipe - 22625 m(Nerkunam head works to Udayanatham Booster Station I).

Collection Sump at Melvalai for Kandachipuram and Melvalai

Tapping Point : At LS 17445 m
Collection Sump : 6.50m dia & 3.45m. Depth of 0.60 Lakh Litre capacity.
Pump Set : 2 Nos. of 10 HP Submersible pumpset of 770 lpm against a head of 45m (One as stand bye).

Booster Station - I

Location : Mugaiyur Village at LS 9730m.
Sump : 6.00m dia & 3.80m depth of 1.00 LL cap.
Pumpset : 2 Nos.of 25 HP Centrifugal pumpset of duty 3100 lpm x 25m head.

Booster station - II

Location : Udayanatham village at LS 22625m
Sump : 6.50m dia & 3.45m. Depth of 1.00 lakh litre capacity
Pumpset : 2 Nos.of 40 HP Centrifugal pumpset of duty 2500 lpm against a head of 38m (one as stand bye).

Pumping Main : : Reach-II

LS 40630 - LS 49985m (LS 40630m to LS 48605m - 250mm. AC Cl.10 Pipe - 7975m. & LS 48605m to 49985m - 200mm. AC Cl.10 pipe - 1280m)

Booster Station - III

Location : Athiyur Village at LS 40630 M.
Sump : 6.50m.dia & 3.45m depth of 1.00 lakh litre capacity
Pumpset : 2 Nos.of 15 HP Centrifugal pumpset of duty 1576 lpm against a head of 24m (one as stand bye).

Pumping Main : : Reach-III

LS 40630 - LS 49985m (LS 40630m to LS 48605m - 250mm. AC Cl.10 Pipe - 7975m. & LS 48605m to 49985m - 200mm. AC Cl.10 pipe - 1280m)

Serivce Reservoirs

6,00,000 lit : 1 nos
1,00,000 lit : 7 nos
60,000 lit : 3 nos
30,000 lit : 4 nos
10,000 lit : 1 nos
Total : 17 Nos